The material and information contained on this website is for general information purposes only. ISA blog posts may be authored by ISA staff and guest authors from the automation community. Views and opinions expressed by a guest author are solely their own, and do not necessarily represent those of ISA. Posts made by guest authors have been subject to peer review.

All Posts

The Importance of Using Tuned Positioners on All Control Valves

 

The following tip is from the ISA book by Greg McMillan and Hunter Vegas titled 101 Tips for a Successful Automation Career, inspired by the ISA Mentor Program. This is Tip #82, and was written by Greg.

 

I was encouraged to omit positioners in one of my first projects in the 1970s as lead instrument engineer. A former power system maintenance technician taking a new career path in instrument maintenance decided that positioners would add unnecessary complexity and aggravation. Fortunately, the request that valves not have positioners occurred after the project was completed. In the days of pneumatic positioners, adjusting the links and pneumatic relays required special skills. Positioners got out of calibration within six months and the lack of position readback made maintenance more difficult and the value of the positioner more questionable.

 

The lead instrument engineer of the system integrator for my next project proposed various ways to reduce project costs. While he had good intentions and was very experienced, all of his suggestions that were implemented created problems that had to be corrected during commissioning and after start-up. One suggestion was that we should put positioners only on selected control valves based on a frequency response study from a noted technologist that showed that boosters should be used instead of positioners on fast loops. However, I found that many rotary valves did not open until the current to pneumatic (I/P) transducer output was 30 percent. During startup, we put positioners on most of the valves.

When I was promoted into Engineering Technology, my areas of expertise came to include exceptionally fast loops such as compressor surge control and phosphorous furnace pressure control. These loops were so fast that they required analog or exceptionally fast digital PID execution times. On particularly large compressors, I recommended that the 24-inch butterfly surge valves have their positioners replaced with boosters (as indicated by the frequency response study mentioned above). The surge valves inexplicably slammed shut. When I went to the field the next day, the technician showed me how he could manually move a big butterfly that had a booster by just grabbing the stem, whereas the butterfly with a positioner could not be moved by hand. I realized that putting a booster on an actuator without a positioner could create positive feedback, where the booster would assist to continue movement.

The booster had assisted some turbulence-induced movement to the closed position. I subsequently dug up a 1958 article (Reference 34) which showed that you should not eliminate the positioner and should put the booster on the output of the positioner with a bypass valve slightly open. A few years later, when I had specified a fast stroking time for furnace pressure control, the supplier put boosters without positioners on the big butterfly valves. In a test at the factory, I showed how I could manually move the big valves and showed them the article. The boosters were then put on the positioner output and the booster bypass valves were tuned for a fast, stable response.

Concept: Today’s smart digital positioners hold their calibration and offer diagnostics and flexible tuning. The speed of response of a valve can be increased by putting a booster on the positioner output and tuning the bypass valve and positioner response settings. However, the tuning rules are not extensively documented. Field support and training schools by the supplier currently provide the required expertise to get the most out of a positioner. External-reset feedback and fast readback can prevent a process PID controller from changing faster than the valve can respond due to size or tuning.

Details: The threshold sensitivity is about 0.1% for digital positioners, 0.2% for two stage high gain relay pneumatic positioners, and 2% for spool type pneumatic positioners. Use digital positioners. Tune a positioner on the valve before installation. After installation at operating temperature and pressure, tune the positioner again. Avoid integral action. If integral action must be used, set the integral deadband in the positioner to stop limit cycles. If the valve must be speeded up, install a booster with a bypass on each positioner output that goes to the actuator.

Double-acting piston actuators require two outputs and hence two boosters. Use a booster with a deadband for piston actuators. For all types of actuators, open the booster bypass valve just enough to prevent rapid cycling of the valve (e.g., 1 cycle per second). Specify a pre-stroke deadtime and slewing rate for large valves. For fast loops, test the positioner tuning to ensure that the valve response is faster than the process controller response. If the control valve response cannot be made fast enough, add an exceptionally fast position readback with external-reset feedback per Tip #85 or detune the process controller to prevent a burst of oscillations from the process controller output changing faster than the control valve can respond in the event of large setpoint changes or big disturbances.

 

Watch-outs: Poor actuator or valve design or sizing can limit what a positioner can do (Tip #81). Positioner readback is on actuator shaft position and not internal flow element (e.g., ball, butterfly, or rotary plug) position. For on-off valves, the difference in position between the internal flow element and the actuator shaft can be as large as 8%, leading to a deadband or stick-slip of 8% from backlash and shaft windup (Tip #83). For on-off valves showing deadband and stick-slip, diagnostics and trend charts within the positioner may indicate that the deadband and stick-slip are an order of magnitude less than actual. Even the smartest and most advanced positioner will give erroneous performance results under such conditions. Thus, putting a great positioner on a control valve may not solve all response problems.

Exceptions: If a PID execution time is smaller than 0.1 seconds or an analog controller is required for good control, a variable speed drive with no deadband or rate limiting in the drive setup is needed. Loops that are too fast for digital PID and hence for control valves (analog control holdouts) are noted in the Control Talk blog What is the Best PID Execution Time?

Insight: Readback control of valve position compensates for a whole host of unknowns in connection with valve response but a positioner, like a controller, must be tuned.

Rule of Thumb: Use tuned positioners on all control valves and add boosters with tuned bypass valves on positioner outputs as necessary to speed up valve response.

 

About the Author
Gregory K. McMillan, CAP, is a retired Senior Fellow from Solutia/Monsanto where he worked in engineering technology on process control improvement. Greg was also an affiliate professor for Washington University in Saint Louis. Greg is an ISA Fellow and received the ISA Kermit Fischer Environmental Award for pH control in 1991, the Control magazine Engineer of the Year award for the process industry in 1994, was inducted into the Control magazine Process Automation Hall of Fame in 2001, was honored by InTech magazine in 2003 as one of the most influential innovators in automation, and received the ISA Life Achievement Award in 2010. Greg is the author of numerous books on process control, including Advances in Reactor Measurement and Control and Essentials of Modern Measurements and Final Elements in the Process Industry. Greg has been the monthly "Control Talk" columnist for Control magazine since 2002. Presently, Greg is a part time modeling and control consultant in Technology for Process Simulation for Emerson Automation Solutions specializing in the use of the virtual plant for exploring new opportunities. He spends most of his time writing, teaching and leading the ISA Mentor Program he founded in 2011.

 

Connect with Greg
LinkedIn

 

Hunter Vegas, P.E., holds a B.S.E.E. degree from Tulane University and an M.B.A. from Wake Forest University. His job titles have included instrument engineer, production engineer, instrumentation group leader, principal automation engineer, and unit production manager. In 2001, he joined Avid Solutions, Inc., as an engineering manager and lead project engineer, where he works today. Hunter has executed nearly 2,000 instrumentation and control projects over his career, with budgets ranging from a few thousand to millions of dollars. He is proficient in field instrumentation sizing and selection, safety interlock design, electrical design, advanced control strategy, and numerous control system hardware and software platforms.

 

Connect with Hunter
LinkedIn

 

Greg McMillan
Greg McMillan
Greg McMillan has more than 50 years of experience in industrial process automation, with an emphasis on the synergy of dynamic modeling and process control. He retired as a Senior Fellow from Solutia and a senior principal software engineer from Emerson Process Systems and Solutions. He was also an adjunct professor in the Washington University Saint Louis Chemical Engineering department from 2001 to 2004. Greg is the author of numerous ISA books and columns on process control, and he has been the monthly Control Talk columnist for Control magazine since 2002. He is the leader of the monthly ISA “Ask the Automation Pros” Q&A posts that began as a series of Mentor Program Q&A posts in 2014. He started and guided the ISA Standards and Practices committee on ISA-TR5.9-2023, PID Algorithms and Performance Technical Report, and he wrote “Annex A - Valve Response and Control Loop Performance, Sources, Consequences, Fixes, and Specifications” in ISA-TR75.25.02-2000 (R2023), Control Valve Response Measurement from Step Inputs. Greg’s achievements include the ISA Kermit Fischer Environmental Award for pH control in 1991, appointment to ISA Fellow in 1991, the Control magazine Engineer of the Year Award for the Process Industry in 1994, induction into the Control magazine Process Automation Hall of Fame in 2001, selection as one of InTech magazine’s 50 Most Influential Innovators in 2003, several ISA Raymond D. Molloy awards for bestselling books of the year, the ISA Life Achievement Award in 2010, the ISA Mentoring Excellence award in 2020, and the ISA Standards Achievement Award in 2023. He has a BS in engineering physics from Kansas University and an MS in control theory from Missouri University of Science and Technology, both with emphasis on industrial processes.

Books:

Advances in Reactor Measurement and Control
Good Tuning: A Pocket Guide, Fourth Edition
New Directions in Bioprocess Modeling and Control: Maximizing Process Analytical Technology Benefits, Second Edition
Essentials of Modern Measurements and Final Elements in the Process Industry: A Guide to Design, Configuration, Installation, and Maintenance
101 Tips for a Successful Automation Career
Advanced pH Measurement and Control: Digital Twin Synergy and Advances in Technology, Fourth Edition
The Funnier Side of Retirement for Engineers and People of the Technical Persuasion
The Life and Times of an Automation Professional - An Illustrated Guide
Advanced Temperature Measurement and Control, Second Edition
Models Unleashed: Virtual Plant and Model Predictive Control Applications

Related Posts

Checking In With Mimo, ISA's Large Language Model Trained on ISA Content

Over the summer of 2024, the International Society of Automation (ISA) announced a large language model (...
Kara Phelps Nov 15, 2024 7:00:00 AM

Ask the Automation Pros: The Use of Artificial Intelligence in Process Control

The following discussion is part of an occasional series, "Ask the Automation Pros," authored by Greg McM...
Greg McMillan Nov 12, 2024 4:30:00 PM

Protecting Electrical Terminal Blocks From Tampering

Electrical terminal blocks are a common sight in the automation world. Usually mounted on DIN rail in ind...
Anna Goncharova Nov 8, 2024 10:30:00 AM