The material and information contained on this website is for general information purposes only. ISA blog posts may be authored by ISA staff and guest authors from the automation community. Views and opinions expressed by a guest author are solely their own, and do not necessarily represent those of ISA. Posts made by guest authors have been subject to peer review.

All Posts

A Simple Approach to Suppression and Elevation in Process Control

This post was authored by Chuck Kirby of ISA.

Suppressed and elevated ranges. The process control industry seems to make a big deal about this subject, certainly important if you are taking the CCST exam, and people get confused. Technicians tend to over think it and over complicate the issue; it is much easier than many try to make it seem.

differential-pressure-transmitter-measuring-level-ttank

There is a very simple test to this question, ask yourself, where is real zero, relative to the lower range value (LRV) If the real zero is above the LRV , somewhere between the LRV and URV, you have an elevated range. If real zero is under the lower range value, you have a suppressed range. Let’s consider the following: I have a transmitter with a range of -10 to +50, real zero is above -10 so we have an elevated zero range. Conversely a range of +50 to +100 has a suppressed zero because real zero is below +50, the LRV. After you determine your LRV and URV it is relatively simple to decide if you have an elevated or suppressed range.

Let’s apply this to a differential pressure transmitter measuring the level of a tank. One side of the transmitter is vented to atmosphere, the other is measuring the head of liquid in the tank

 The transmitter is mounted 24” below the tank empty. This tank has a 120” span. The LRV is 24”, the URV is 144. Where is real zero? It is below the LRV of 24” so we have a suppressed zero range.  There you have it, very simple.


Related Posts

Checking In With Mimo, ISA's Large Language Model Trained on ISA Content

Over the summer of 2024, the International Society of Automation (ISA) announced a large language model (...
Kara Phelps Nov 15, 2024 7:00:00 AM

Ask the Automation Pros: The Use of Artificial Intelligence in Process Control

The following discussion is part of an occasional series, "Ask the Automation Pros," authored by Greg McM...
Greg McMillan Nov 12, 2024 4:30:00 PM

Protecting Electrical Terminal Blocks From Tampering

Electrical terminal blocks are a common sight in the automation world. Usually mounted on DIN rail in ind...
Anna Goncharova Nov 8, 2024 10:30:00 AM