The material and information contained on this website is for general information purposes only. ISA blog posts may be authored by ISA staff and guest authors from the automation community. Views and opinions expressed by a guest author are solely their own, and do not necessarily represent those of ISA. Posts made by guest authors have been subject to peer review.

All Posts

AutoQuiz: How to Calibrate a High-Range Electronic Pressure Transmitter

 

AutoQuiz is edited by Joel Don, ISA's social media community manager.

 

This automation industry quiz question comes from the ISA Certified Control Systems Technician (CCST) program. Certified Control System Technicians calibrate, document, troubleshoot, and repair/replace instrumentation for systems that measure and control level, temperature, pressure, flow, and other process variables. Click this link for more information about the CCST program.

 

 

Which of the following calibration instruments will be the best choice to calibrate a high-range electronic pressure transmitter for a range of 0–1000 psig?

a) decade box
b) squeeze bulb
c) function generator
d) dead-weight tester
e) none of the above

 

A squeeze bulb can only be used to generate pressures for calibration in the range of 0–500 inH2O (~18 psig).

A decade box is used to calibrate temperature transmitters and instruments and cannot be used for pressure calibration.

A function generator is a piece of electronic test equipment or software used to generate different types of electrical waveforms over a wide range of frequencies, and therefore cannot be used for pressure calibration.

The correct answer is D, dead-weight tester. A dead-weight tester apparatus uses known traceable weights to apply pressure to a fluid for checking the accuracy of readings from a pressure gauge or pressure transmitter. Due to the force-multiplying properties of a dead-weight tester, these primary calibration instruments can typically be used to generate accurate test pressures from 15–10,000 psig.

 

Reference: Goettsche, L.D. (Editor), Maintenance of Instruments and Systems, 2nd Edition

 

About the Editor
Joel Don is the community manager for ISA and is an independent content marketing, social media and public relations consultant. Prior to his work in marketing and PR, Joel served as an editor for regional newspapers and national magazines throughout the U.S. He earned a master's degree from the Medill School at Northwestern University with a focus on science, engineering and biomedical marketing communications, and a bachelor of science degree from UC San Diego.

 

Connect with Joel
LinkedInTwitterEmail

 

 

Joel Don
Joel Don
Joel Don is an independent content marketing, social media and public relations consultant. Prior to his work in marketing and PR, Joel served as an editor for regional newspapers and national magazines throughout the U.S. He earned a master's degree from the Medill School at Northwestern University with a focus on science, engineering and biomedical marketing communications, and a bachelor of science degree from UC San Diego.

Related Posts

How Did Automation Professionals Benefit from ISA in 2024?

The International Society of Automation (ISA) is proud to be the professional home of thousands of member...
Kara Phelps Dec 17, 2024 9:30:00 AM

Ensuring RCM or DCS Redundancy and Its Security in a Complex Industrial Environment

In industrial automation, remote control managers (RCM) or distributed control systems (DCS) are critical...
Ashraf Sainudeen Dec 13, 2024 10:00:00 AM

ISA Podcast Explores Automation and Smart Agriculture

The International Society of Automation (ISA) podcast, Podomation, curates and shares insightful discussi...
Kara Phelps Dec 10, 2024 11:00:00 AM